Tilting disc check valves
A disc on an offset pivot that tips open with the flow and tips shut before the flow can run back.
Tilting disc check valves are classified in several ways at once: by how the pivot pin is arranged, by what helps the disc to close, by the body, and by the seat. Each option below has its own 3D cutaway.
11. By pivot: inside or through the body
The pivot pin can stay sealed inside the body, or pass out through it so something outside can act on the disc.
Internal pivot
The pivot pin is held inside the body, with plugs in the ends of its holes.
How it works
The pin and its bushes are carried in bosses in the body wall and both ends are plugged. Nothing passes through the wall.
Strengths
- ✓No leak path along the pin.
- ✓Fewer parts and no packing to maintain.
- ✓Cheaper.
Limits
- !Nothing outside shows the disc position.
- !No lever, weight or damper can be fitted.
Where it is used
- •Clean water and general lines.
- •Moderate sizes.
External pivot (through pin)
The pivot pin passes out through the body, through a packed boss.
How it works
A packing and gland seal the pin where it leaves the body. Outside, an indicator, a lever with a weight, or a lever with a dashpot can be fitted.
Strengths
- ✓The disc position can be seen from outside.
- ✓Lets a closing aid be fitted.
- ✓The disc can be adjusted without opening the valve.
Limits
- !A packing that can leak.
- !More parts and more cost.
Where it is used
- •Large pump discharge lines.
- •Pipelines with a long, fast stop.
22. By what helps it close
A tilting disc already closes fast, because it travels only a short way. On very large lines or after a hard stop it can still be given help.
No aid (gravity)
The disc tips shut by its own weight and the inclined seat.
How it works
The disc is hung above its centre on an inclined seat. When the flow slows, gravity tips it back to the seat.
Strengths
- ✓Simplest and cheapest.
- ✓Closes fast already, with a short travel.
- ✓No outside parts.
Limits
- !On a very fast stop in a long line it can still hit the seat.
- !Nothing to cushion the end.
Where it is used
- •Most pump lines.
- •Gravity and low-pressure lines.
Outside lever and counterweight
A lever on the pin carries a weight that tips the disc shut sooner.
How it works
The weight acts through the lever, so the disc starts to close as the flow slows, before it reverses.
Strengths
- ✓Closes even sooner.
- ✓Easy to adjust by sliding the weight.
- ✓Shows the disc position.
Limits
- !Raises the flow needed to hold the disc open.
- !Takes room at the side.
Where it is used
- •Pump stations with a hard stop.
- •Water lines.
Lever with oil dashpot
A lever, weight and an oil damper that cushions the last part of the tilt.
How it works
The weight starts the closing, and the damper slows the disc just before it seats, so it lands softly.
Strengths
- ✓Cuts the closing surge a lot.
- ✓Adjustable damping.
Limits
- !More parts and oil to maintain.
- !Needs more room at the side.
Where it is used
- •Very large pipelines.
- •Long transmission mains.
33. By body: flanged, wafer or weld ends
The body decides the size, weight and pressure the valve can take, and how it joins the pipe.
Flanged
A full body with flanges, bolted to the pipe flanges.
How it works
The flanged body carries the seat and pivot bosses, and is bolted between the pipe flanges. It can be taken out as a unit.
Strengths
- ✓Every size and rating.
- ✓Strong and long-lasting.
- ✓Easy to fit and replace.
Limits
- !Long and heavy.
- !Dear in large sizes.
Where it is used
- •Most pump and pipeline duties.
- •Large sizes.
Wafer (slimline)
A short body between the pipe flanges, held by the flange bolts.
How it works
The valve has no flanges of its own. The disc and pivot sit in a slim ring, and the pipe bolts hold it.
Strengths
- ✓Light, short and cheap.
- ✓Fits where space is tight.
Limits
- !A higher loss and a limit on size and pressure.
- !Cannot be serviced in line.
Where it is used
- •Small and medium water lines.
- •Low pressure.
Weld ends
A body with butt-weld ends, welded into the pipe.
How it works
The body ends are bevelled for welding, so there is no flange joint to leak. The body can be opened for service.
Strengths
- ✓For very high pressure and temperature.
- ✓No flange joint to leak.
Limits
- !Dear.
- !Harder to remove.
Where it is used
- •Power plants and high-pressure pipelines.
- •Buried lines.
44. By seat: metal or resilient
The seat is what the disc closes on. It decides the tightness and the temperature the valve can take.
Metal seat
A hard metal disc seats on a hard metal ring.
How it works
The two faces are machined or hard-faced to match. The seal is metal on metal, so it is strong but not perfectly tight.
Strengths
- ✓Strong and long-lasting.
- ✓Takes high temperature and dirty fluids.
- ✓Little wear.
Limits
- !A small leak is normal.
- !Needs a clean, smooth seat.
Where it is used
- •Steam, oil, gas and hot water.
- •Dirty fluids.
Resilient (rubber-faced) seat
A rubber face on the disc presses into the seat.
How it works
The rubber is squeezed by the back pressure and fills small scratches, so the valve seals drop-tight.
Strengths
- ✓Drop-tight shut-off.
- ✓Quiet closing.
- ✓Seals past small grit.
Limits
- !Limited temperature.
- !The rubber ages and can be cut.
Where it is used
- •Water lines.
- •Cold, clean liquids.
Metal (13 % chrome or bronze)
Hard and strong. Good for hot water, oil and gas up to about 425 °C. Leaks a little.
Typical use: steam, hot water, oil, general service
Hard-faced metal
A very hard alloy welded on the seat and disc. For high temperature and wear.
Typical use: steam, high temperature, erosive fluids
EPDM rubber
Water, seawater and sewage up to about 120 °C. Not for oil.
Typical use: water supply, sewage
NBR (nitrile)
Oil, fuel and gas up to about 100 °C. Not for sunlight or strong acids.
Typical use: oil, fuel, air and gas lines
FKM (fluoroelastomer)
Oil, fuels and many chemicals up to about 200 °C. Dearer.
Typical use: chemicals, hot oils
55. Disc and pin materials
The disc, arm and hinge pin are wet by the fluid and rub against each other, so their material matters as much as the body.
Bronze
Good for fresh and raw water. Not for seawater with fast flow, strong chemicals or steam.
Typical use: water supply, fire lines
Stainless steel 304
Water, air, oil and mild chemicals.
Typical use: general service
Stainless steel 316
Chemicals, chlorides and hot service.
Typical use: process and hot lines
Duplex stainless steel
Seawater and high chloride fluids. Strong and resistant.
Typical use: seawater, offshore
66. Standards
These are the main standards a specification or datasheet refers to.
| Standard | Covers | Typical use |
|---|---|---|
| API 594 | Check valves: flanged, lug, wafer and butt-welding | Process plants and pipelines |
| API 6D / ISO 14313 | Pipeline valves, including check valves | Oil, gas and water pipelines |
| AWWA C508 | Check valves for waterworks | Water supply |
| ASME B16.34 | Pressure-temperature ratings of valves | Rating selection |
| API 598 / EN 12266 | Shell and seat tests, and leakage classes | Acceptance testing |
Check the current edition and the project specification: they decide which standard applies.
77. Why this model and not another?
A tilting disc is the choice for large pump lines, but not for every duty. Here is how to choose.
| If your duty is… | Tilting disc | Swing check | Dual-plate | Nozzle |
|---|---|---|---|---|
| Very large pump discharge line | Best choice | Heavy and slow | Heavy | Good |
| Pump that may stop fast | Good: closes early | Needs lever and dashpot | Good | Best choice |
| Water or sewage with solids | Poor: pivot can jam | Best choice | Poor | Poor |
| Small line, low cost | Dear | Best choice | Good | Fair |
| Compact, light valve | Wafer type is fair | Wafer is fair | Best choice | Fair |
| Pulsating flow (reciprocating pump) | Poor | Poor | Poor | Fair |
| Steady, clean water at a low flow | Good: opens at a low flow | Poor: disc flutters | Fair | Good |
Choose a tilting disc when…
Choose it when
- ✓The pipe is large and the pump can stop fast.
- ✓You need low slam and a quick close.
- ✓The fluid is clean.
- ✓You want low loss.
Do not choose it when
- ✗Solids, sewage or slurry.
- ✗Pulsating flow from a reciprocating pump.
- ✗A small line, where a swing check is cheaper.
Choose a swing check when…
Choose it when
- ✓The fluid has solids.
- ✓The line is short and the stop is gentle.
- ✓You want the cheapest simple valve.
Do not choose it when
- ✗Long pump lines that stop fast, without an aid.
- ✗Very low flow.
Choose a dual-plate or nozzle when…
Choose it when
- ✓Space and weight matter.
- ✓You need the lowest slam (nozzle).
- ✓The fluid is clean.
Do not choose it when
- ✗Solids and sewage.
- ✗A tight budget for a simple job.
Common mistakes
- !Using a tilting disc on a sewage line: the pivot and seat can jam with rags.
- !Choosing the check valve at the pipe size: at low flow the disc rests part-open.
- !Fitting it the wrong way up, so the pivot is below the centre.
- !Using it on a reciprocating pump: the pulses make the disc chatter.
- !Forgetting the lever and dashpot on a very large line with a fast pump trip.
💡 Rule of thumb: tilting disc for large, clean pump lines with a fast stop; swing check where there are solids; nozzle where the stop is the fastest.