← Regulating (throttling) valves

The question it answers

Classification by flow characteristic

How does the flow change as the valve opens?

A control valve is useful only if turning it a little changes the flow by a predictable amount. The shape of the plug, and the way the pressure drop shifts as it opens, decide that. This is the valve's characteristic, and it is chosen to suit the system the valve sits in.

1The options in detail

1

Linear

The flow rises in direct proportion to the opening: twice the lift, twice the flow, when the pressure drop across the valve stays the same.

OpenSupply side: 6.0 bar
Far side: 6.0 bar
Drag to rotate · hover a dot for its name
LinearEqual percentageQuick openingValve openingFlow

How it works

The plug is shaped so that the open area grows in a straight line with its lift. The curve on the chart is a straight line, and every step of opening adds the same extra flow.

Strengths

  • ✓Easy to understand and to tune.
  • ✓Good where the pressure drop across the valve stays roughly constant.
  • ✓Suits level and flow control with a steady supply.

Limits

  • !Gain is high at small openings if the valve is oversized.
  • !Not ideal where the pressure drop changes a lot.

Where it is used

  • •Liquid level control.
  • •Flow loops with a fixed pump head.
2

Equal percentage

Each equal step of opening increases the flow by the same percentage of the flow already passing. The curve is gentle at the start and steep at the end.

OpenSupply side: 6.0 bar
Far side: 6.0 bar
Drag to rotate · hover a dot for its name
LinearEqual percentageQuick openingValve openingFlow

How it works

The plug is shaped like a slim parabola, so the opening grows slowly at first and faster later. In a real pipe most of the pressure is lost in the pipe itself as the valve opens, and this characteristic cancels that and makes the whole loop behave almost linearly.

Strengths

  • ✓Steady control over a very wide range, often 50 to 1.
  • ✓Forgiving where the pressure drop across the valve falls as it opens.
  • ✓The usual choice for pumped systems and temperature loops.

Limits

  • !Very small openings change the flow very little.
  • !Needs careful sizing, or the top end becomes touchy.

Where it is used

  • •Pressure control.
  • •Temperature loops and pumped lines.
3

Quick opening

A small lift gives most of the flow at once. The curve rises steeply, then flattens.

OpenSupply side: 6.0 bar
Far side: 6.0 bar
Drag to rotate · hover a dot for its name
LinearEqual percentageQuick openingValve openingFlow

How it works

The plug is a flat disc or a very short plug, so the open area is nearly all there after only a short lift. It works almost like an on-off valve with a little throttling.

Strengths

  • ✓Full flow with very little travel.
  • ✓Good for on-off and relief duties.
  • ✓Simple and cheap.

Limits

  • !Poor control over most of the range.
  • !Tends to hunt in a loop.

Where it is used

  • •Safety and relief duties.
  • •Systems that switch quickly between on and off.

How to choose

  • →Pressure drop across the valve stays constant: linear.
  • →Pressure drop across the valve changes a lot, or the loop has a pipe in series: equal percentage.
  • →You want on-off with a little throttling: quick opening.

Common mistakes

  • !Choosing a valve that is too big, so it works at a few percent open.
  • !Using a linear valve where most of the pressure is lost elsewhere in the system.
  • !Ignoring how the characteristic changes once it is installed.