The question it answers
Classification by trim and guiding
How are the plug and seat arranged?
The trim is the set of parts that the fluid actually touches: the plug, the seat and sometimes a cage. How they are arranged decides the force the actuator needs, how tightly the valve shuts and how steadily the plug moves.
1The options in detail
Single seat
One plug closes on one seat ring.
Far side: 6.0 barDrag to rotate · hover a dot for its name
How it works
The pressure of the fluid acts on the whole area of the plug and pushes against the stem. The valve seals very tightly because there is only one seating line to match.
Strengths
- ✓Tight shut-off.
- ✓Simple, easy to maintain.
- ✓Cheaper than a balanced trim.
Limits
- !The actuator must overcome the pressure force.
- !Large valves at high pressure need big actuators.
Where it is used
- •Small and medium valves.
- •Duties that need shut-off.
Double seat
Two plugs on one stem close on two seats, one above the other.
Far side: 6.0 barDrag to rotate · hover a dot for its name
How it works
The fluid pushes one plug up and the other down, so the forces mostly cancel. The actuator needs far less force. But two seats never touch at exactly the same moment, so shut-off is poorer.
Strengths
- ✓Balanced, so low actuator force.
- ✓Large flow in a compact body.
- ✓Good for big pressure differences.
Limits
- !Not tight when closed.
- !Differences in expansion can make the seats leak.
Where it is used
- •Large control valves.
- •Where leakage is acceptable.
Cage-guided (balanced)
The plug slides like a piston inside a cylindrical cage with holes or slots in its wall.
Far side: 6.0 barDrag to rotate · hover a dot for its name
How it works
The holes in the cage set the flow area, and a seal ring on the plug stops fluid slipping past it. Pressure acts above and below the plug, so it is balanced, and the cage guides it so it does not rattle.
Strengths
- ✓Balanced, with good shut-off from a seal ring.
- ✓Steady and quiet.
- ✓Trim can be swapped, giving other characteristics.
Limits
- !More parts to wear and clog.
- !Not for dirty fluids.
Where it is used
- •Clean liquids, steam and gas.
- •High pressure and noisy duties.
How to choose
- →Shut-off is vital: single seat.
- →Large valve, low actuator force, leakage tolerable: double seat.
- →Balanced and quiet with good shut-off: cage-guided.
Common mistakes
- !Expecting a double-seat valve to shut tight.
- !Using a cage trim on a dirty fluid.
- !Choosing a small actuator for a single-seat valve at high pressure.