← Non-return valves

Tilting disc check valves

A disc on an offset pivot that tips open with the flow and tips shut before the flow can run back.

Your dutyClean waterDN 40010 bar20 °C1000 m³/hEdit duty

Step 5 of 6

5Calculations

Three checks make the selection safe: the flow and pressure drop, whether the flow is enough to hold the disc open, and the closing surge when the pump stops.

1. Flow and pressure drop

Kv = 0.04·DN² / √ζ   ·   Cv = 1.156·Kv   ·   ΔP = ζ·ρ·v² / 2

Density
1,000 kg/m³
Velocity
2.21 m/s
ζ
1.40
Kv / Cv
5,409 / 6,253
ΔP
0.034 bar
Drop with the disc fully open
0.034 bar
OKVelocity at most 3 m/s

2. Holding the disc open

vmin = 35·√V (ft/s), V = specific volume (ft³/lb)

Minimum velocity to hold it open
1.11 m/s
Velocity
2.21 m/s
How far the disc is held open
100 %
Cracking pressure
40 mbar
OKThe flow is enough to hold the disc fully open.

Typical figures. The cracking pressure is the very small pressure difference that first tips the disc open; a soft seat and a counterweight make it a little higher. The maker's data decides.

3. Closing surge (slam)

a = (P/ρ)/L ≤ v/0.5   ·   vrev = a·tclose   ·   ΔP = ρ·c·vimpact

Wave speed
1000 m/s
How fast the flow slows
1.67 m/s²
Time for the disc to tip shut
0.10 s
Reverse velocity as it closes
0.17 m/s
Velocity at impact (after cushioning)
0.17 m/s
Closing surge
1.7 bar
Allowed surge
2.0 bar
OKThe closing surge is within the allowed value.

Typical – not brand data. This is a pre-selection. Confirm the final choice with the manufacturer and the project specification.