Air valves
Valves at the high points of a water pipe that let air out and in: small automatic air release valves, large air and vacuum valves, and double- and triple-function valves that do both.
Step 2 of 6
2Type
First decide whether an air release valve is the right valve, then choose the mechanism, the body and the orifice.
Suitability of an air release valve
Good fitAn air release valve is a good choice for this duty.
Why
- →Air gathers at the high points of a pipe. An air release valve belongs there.
- →About 2 % of the water flow, by volume, comes out of the water as air. That is the air the valve must let out.
- →A float on the water level opens and closes the valve by itself. It needs no power.
- →The orifice is small because the pressure pushes on it. The bigger it is, the lower the pressure the valve can hold.
- →The mechanism is chosen from the pressure: a direct float to about 2 bar, a lever to about 16 bar, a compound lever above.
- →It lets air out but cannot let air in. Where the pipe can drain, add an air and vacuum valve.
- →Always fit an isolating valve under the air valve, so it can be serviced while the pipe is under pressure.
- →In clean water a small orifice with a rubber seal is a good choice.
Consider also
- Combination air valve
Your valve
Recommended values are filled in. Change any of them and the checks update.
- Function
- An air release valve: lets out small pockets of air under pressure. Enough for a small main that does not drain.
- Mechanism
- A lever: multiplies the float's force, for pressures up to about 16 bar.
- Body
- A plastic body: does not corrode, for irrigation and small water pipes.
- Orifice
- The orifice is the smallest that passes the air and that the float can hold at this pressure.
What to ask for in the specification
These follow from the duty. Put them on the datasheet.
- ✓Position. Fit it at the high points, and every 400 to 800 m on a long level run, on a rising or falling grade change, and after long descents.
- ✓Isolating valve. A ball or gate valve under the air valve, so it can be taken off and serviced while the pipe is under pressure.
- ✓Vacuum protection. An air release valve does not let air in. Where the pipe can drain or a vacuum can form, add an air and vacuum valve or use a combination valve.
- ✓Drain and chamber. Fit a drain or a flush connection, and keep the chamber clear of water: a flooded outlet lets dirty water into the pipe.
- ✓Test. The valve is tested for shell strength, seat leakage and float function before it is shipped.
See all types with 3D models →
Typical – not brand data. This is a pre-selection. Confirm the final choice with the manufacturer and the project specification.