Foot valves
A check valve with a strainer on the end of a pump's suction pipe: it keeps the rubbish out and the pipe full.
Step 5 of 6
5Calculations
Three checks make the selection safe: the flow, the pressure drop and the suction limit, whether the flow lifts the disc, and the closing surge when the pump stops.
1. Flow and pressure drop
Kv = 0.04·DN² / √ζ · Cv = 1.156·Kv · ΔP = ζ·ρ·v² / 2
- Density
- 1,000 kg/m³
- Velocity
- 2.48 m/s
- ζ
- 3.77
- Kv / Cv
- 206 / 238
- ΔP
- 0.12 bar
- Drop with the disc fully lifted
- 0.12 bar
- Strainer open area, and hole size
- 4 × pipe area · 3 mm
- Drop with the strainer half blocked
- 0.13 bar
OKVelocity at most 3 m/s
CHECKThe suction velocity should stay below 1.5 m/sOKWith the strainer half blocked the drop should stay below 0.3 bar
- !The velocity is above 1.5 m/s, which is too fast for a suction pipe. The pump has no pressure to spare, and it will cavitate. Use a larger foot valve and suction pipe.
2. Holding the disc lifted
vmin = 35·√V (ft/s), V = specific volume (ft³/lb)
- Minimum velocity to hold it open
- 2.12 m/s
- Velocity
- 2.48 m/s
- How far the disc is lifted
- 100 %
- Cracking pressure
- 24 mbar
OKThe flow is enough to hold the disc fully lifted.
Typical figures. The cracking pressure is set by the weight of the disc and the spring: it is the suction that first lifts the disc. The maker's data decides.
3. Closing surge (slam)
a = (P/ρ)/L ≤ v/0.5 · vrev = a·tclose · ΔP = ρ·c·vimpact
- Wave speed
- 1000 m/s
- How fast the flow slows
- 3.33 m/s²
- Time for the disc to drop back
- 0.09 s
- Reverse velocity as it closes
- 0.30 m/s
- Velocity at impact
- 0.18 m/s
- Closing surge
- 1.8 bar
- Allowed surge
- 2.0 bar
OKThe closing surge is within the allowed value.
Typical – not brand data. This is a pre-selection. Confirm the final choice with the manufacturer and the project specification.