Pressure reducing valves
A self-acting valve that cuts a high supply pressure to a lower, steady one, whatever the supply or the demand does.
Step 5 of 6
5Calculations
These are the checks on the chosen valve. Each shows its formula, the numbers and whether it passes.
1. Flow and opening
Kv = W / (27.3·Y·√(x·P₁·ρ₁)) · Y = 1 − x / (3·Fk·xT) · x = ΔP / P₁ · Kvs = k·DN² · opening = Kv / Kvs
- Pressure drop ΔP
- 3.00 bar (P₁ 8.01 → P₂ 5.01 bar abs)
- Pressure ratio P₁ / P₂ (absolute)
- 1.6 : 1
- Flow
- 600.0 kg/h
- Density at the inlet
- 4.21 kg/m³
- x / Y
- 0.37 / 0.76
- Kv required
- 8.2
- Kvs / Cvs
- 30 / 35
- Opening needed (Kv ÷ Kvs)
- 27 %
Kvs is typical for the design and the size, not brand data. The gas formula is the IEC 60534 one, with the density of the steam or air at the inlet; the steam is taken as saturated at the inlet pressure unless the temperature is changed.
2. Control quality
P₂(Q) = P₂set·(1 − droop·Q/Qmax) · lock-up = P₂set·(1 + k) · ΔP₂ = (Aseat / Adiaphragm)·ΔP₁
- Set pressure
- 4.00 bar g
- Droop at this flow
- 0.20 bar (5 %)
- Outlet pressure at this flow
- 3.80 bar g
- Lock-up pressure (no flow)
- 4.40 bar g
- Outlet shift for a fifth change in the inlet
- 0.06 bar
- Spring range
- 2 – 6 bar g
Droop and lock-up are typical for each design, not brand data. Droop is the fall of the outlet pressure from no flow to full flow; lock-up is the rise above the set pressure at no flow.
3. Outlet velocity, noise and cavitation
v = Q₂ / A · x = ΔP / P₁ (choked when x ≥ Fk·xT)
- Flow after the valve
- 227.6 m³/h (2.64 kg/m³)
- Velocity in the outlet pipe
- 32.2 m/s
- Drop ratio x / limit
- 0.37 / 0.51
The limits are typical. The outlet pipe should be larger than the inlet pipe for steam and gas, because the volume grows as the pressure falls.
4. Protecting the low-pressure side
Qfail = Kvs·√ΔP (or the gas formula at Kvs) · relief needed when P₁ > Pdownstream rating
- Rating of the low-pressure side
- 10.0 bar g
- Flow if the valve fails open
- 2,200 kg/h
The failure flow is the valve's Kvs at the same pressures. Set the relief valve below the rating of the low-pressure pipe.
Typical – not brand data. This is a pre-selection. Confirm the final choice with the manufacturer and the project specification.