Pressure reducing valves
A self-acting valve that cuts a high supply pressure to a lower, steady one, whatever the supply or the demand does.
Step 6 of 6
6Summary
The duty, the choices and the checks together. Copy it, print it, or start again.
Duty
- Fluid
- Steam
- Size
- DN 50
- Pressure
- 7 → 4 bar g
- Temperature
- 170 °C
- Flow
- 600 kg/h
Valve
- Type
- Pressure reducing valve
- Design
- Direct-acting
- Seat
- Metal seat
- Sensing
- External sensing
- Body
- Bronze
- Spring range
- 2 – 6 bar g
Body and rating
- Rating
- 11.2 bar
- Face to face
- 230 mm
Checks
- Kvs
- 30 (Cv 35)
- Opening needed
- 27 %
- Droop
- 0.20 bar
- Lock-up
- 4.40 bar g
- Outlet velocity
- 32.2 m/s
- Failure flow
- 2,200 kg/h
Standards and needs
- Design standard
- EN 1349
- Tests
- EN 12266-1; IEC 60534; ISO 4126-1
- Also needed
- Strainer; Isolation valves; Bypass; Gauges; Straight pipe; Sensing; Spring range; Steam trap; Drain; Slow warm-up; Dry steam
Typical – not brand data. This is a pre-selection. Confirm the final choice with the manufacturer and the project specification.