Pressure reducing valves
A self-acting valve that cuts a high supply pressure to a lower, steady one, whatever the supply or the demand does.
Step 2 of 6
2Type
First decide whether a pressure reducing valve suits the duty, then choose the design, the seat and where the pressure is sensed from.
Is it the right valve?
Good fitA pressure reducing valve is a good choice for this duty.
Why
- →A PRV is self-acting: the pressure after it moves it, so it needs no power and no controller.
- →Steam wants a metal seat or a high-temperature soft seat, a steel or iron body, and a drain and a strainer in front.
- →A direct-acting valve is the simple choice for this duty: it is small, cheap and quick.
- →Steam condenses: fit a drain and a trap in front of the valve so that wet steam does not cut the seat.
Build the valve
The recommended choices are set. Change any of them.
- Design
- Simple, small and cheap. The pressure droops a little as the flow rises.
- Seat
- Stands heat and dirt. Passes a small leak when shut (class IV).
- Sensing
- A sense line from the pipe downstream. Reads the pressure where it is needed.
What the valve needs
These follow from the duty and the choices. Put them on the datasheet and the drawing.
- ✓Strainer. A strainer in front keeps scale and dirt off the seat and out of the pilot. Use a fine mesh in front of a pilot.
- ✓Isolation valves. A valve on each side lets the PRV be taken out for service without stopping the plant.
- ✓Bypass. A bypass with a hand valve keeps the plant running while the PRV is serviced. Never leave it open.
- ✓Gauges. A gauge before and a gauge after the valve, to set it and to see that it holds.
- ✓Straight pipe. A straight run of pipe after the valve, so that the stream settles before the sensing point.
- ✓Sensing. Where the pressure is sensed from: inside the valve, or a line 6 to 10 pipe diameters downstream on a straight run.
- ✓Spring range. The spring is chosen so that the set pressure falls in the middle part of its range.
- ✓Steam trap. A trap in front takes the condensate away so that the valve gets dry steam.
- ✓Drain. A drain at the low point before the valve, so that water is not carried through the seat.
- ✓Slow warm-up. Open the isolation valve slowly on steam, so the valve and the pipe warm up and the condensate drains.
- ✓Dry steam. A separator or a good trap before the valve, because wet steam cuts the seat.
- ✓Leakage class. Name the leakage class: class VI for a soft seat, class IV for a metal seat.
- ✓Spares. Diaphragm, seals, seat and spring are the parts that wear. Keep a set.
Typical – not brand data. This is a pre-selection. Confirm the final choice with the manufacturer and the project specification.