Dual-plate check valves
Two spring-loaded plates that fold open with the flow and snap shut the moment it slows.
Step 5 of 6
5Calculations
Three checks make the selection safe: the flow and pressure drop, whether the flow is enough to hold the plates open against the spring, and the closing surge when the pump stops.
1. Flow and pressure drop
Kv = 0.04·DN² / √ζ · Cv = 1.156·Kv · ΔP = ζ·ρ·v² / 2
- Density
- 1,000 kg/m³
- Velocity
- 2.65 m/s
- ζ
- 2.04
- Kv / Cv
- 1,120 / 1,295
- ΔP
- 0.072 bar
- Drop with the disc fully open
- 0.072 bar
OKVelocity at most 3 m/s
2. Holding the plates open
vmin = 35·√V (ft/s), V = specific volume (ft³/lb)
- Minimum velocity to hold it open
- 1.54 m/s
- Velocity
- 2.65 m/s
- How far the plates are held open
- 100 %
- Cracking pressure
- 48 mbar
OKThe flow is enough to hold the plates fully open.
Typical figures. The cracking pressure is set by the spring: it is the pressure difference that first opens the plates. The maker's data decides.
3. Closing surge (slam)
a = (P/ρ)/L ≤ v/0.5 · vrev = a·tclose · ΔP = ρ·c·vimpact
- Wave speed
- 1000 m/s
- How fast the flow slows
- 3.33 m/s²
- Time for the plates to snap shut
- 0.06 s
- Reverse velocity as it closes
- 0.19 m/s
- Velocity at impact
- 0.19 m/s
- Closing surge
- 1.9 bar
- Allowed surge
- 2.0 bar
OKThe closing surge is within the allowed value.
Typical – not brand data. This is a pre-selection. Confirm the final choice with the manufacturer and the project specification.