Nozzle check valves
A spring-loaded plug that slides along the pipe and shuts before the flow can turn back.
Step 5 of 6
5Calculations
Three checks make the selection safe: the flow and pressure drop, whether the flow is enough to hold the plug open against the spring, and the closing surge when the pump stops.
1. Flow and pressure drop
Kv = 0.04·DN² / √ζ · Cv = 1.156·Kv · ΔP = ζ·ρ·v² / 2
- Density
- 1,000 kg/m³
- Velocity
- 2.65 m/s
- ζ
- 2.30
- Kv / Cv
- 1,055 / 1,220
- ΔP
- 0.081 bar
- Drop with the plug fully open
- 0.081 bar
OKVelocity at most 3 m/s
2. Holding the plug open
vmin = 35·√V (ft/s), V = specific volume (ft³/lb)
- Minimum velocity to hold it open
- 1.11 m/s
- Velocity
- 2.65 m/s
- How far the plug is held open
- 100 %
- Cracking pressure
- 28 mbar
OKThe flow is enough to hold the plug fully open.
Typical figures. The cracking pressure is set by the spring: it is the pressure difference that first lifts the plug. The maker's data decides.
3. Closing surge (slam)
a = (P/ρ)/L ≤ v/0.5 · vrev = a·tclose · ΔP = ρ·c·vimpact
- Wave speed
- 1000 m/s
- How fast the flow slows
- 3.33 m/s²
- Time for the plug to shut
- 0.05 s
- Reverse velocity as it closes
- 0.16 m/s
- Velocity at impact
- 0.10 m/s
- Closing surge
- 1.0 bar
- Allowed surge
- 2.0 bar
OKThe closing surge is within the allowed value.
Typical – not brand data. This is a pre-selection. Confirm the final choice with the manufacturer and the project specification.