← Non-return valves

Nozzle check valves

A spring-loaded plug that slides along the pipe and shuts before the flow can turn back.

Your dutyClean waterDN 20010 bar20 °C300 m³/hEdit duty

Step 2 of 6

2Type

First decide whether a nozzle check is the right check valve, then choose the guide, the spring and the body. The rules below are typical practice; you can override them.

Suitability of a dual-plate check valve

Good fit

A nozzle check is a good choice for this duty.

Why

  • →A nozzle check closes with the least slam of any check valve, because the plug has only a short way to go.
  • →In a pump line it stops the flow running back when the pump stops. Check the closing surge in the last step.
  • →Clean liquid at a steady flow is its best duty: the guide and stem stay clean.

Your valve

Recommended values are filled in. Change any of them and the later steps follow.

Guide
One rear guide: simple, with the lowest loss, for steady and clean flow.
Spring
A weak spring: opens at a very low flow, but closes a little more slowly.
Body
A short body clamped between the pipe flanges: light and cheap, for small and medium lines.

What to ask for in the specification

These follow from the duty. Put them on the datasheet.

  • ✓Spring setting. Set the spring against the closing surge, and check that your normal flow still holds the plug fully open.
  • ✓Guide bush and stem. The stem runs in a bush that wears. Ask for a bush that can be replaced, and a stem with a hard, smooth finish.
  • ✓Straight run. Leave at least five pipe diameters of straight pipe upstream, so the plug is not buffeted by uneven flow.
  • ✓Orientation. The valve works in any position, but check the datasheet for the spring and weight in a vertical line, and keep the arrow on the body pointing with the flow.
  • ✓Flow area. The ring gap round the plug should be at least the area of the pipe, so the valve does not choke the flow.
  • ✓Drain connection. A drain plug lets the body be emptied before it is taken out.
  • ✓Pressure test. Every valve should be shell-tested and seat-tested to API 598 or EN 12266, with a certificate.

See all types with 3D models →

Typical – not brand data. This is a pre-selection. Confirm the final choice with the manufacturer and the project specification.